RUGGEDCOM RMC30
Installation Guide
Chapter 6
Certification
Other Approvals 25
• CAN ICES-3 (A)/NMB-3 (A)
Section6.1.6
Other Approvals
This device meets the requirements of the following additional standards:
• IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
• IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3: General Requirements
Section6.2
EMC and Environmental Type Tests
The RUGGEDCOM RMC30 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test Description Test Levels Severity Levels
Enclosure Contact ± 8 kV 4IEC 61000-4-2 ESD
Enclosure Air ± 15 kV 4
IEC 61000-4-3 Radiated RFI Enclosure Ports 20 V/m Note
a
Signal Ports ± 4 kV @ 2.5 kHz Note
a
DC Power Ports ± 4 kV 4
AC Power Ports ± 4 kV 4
IEC 61000-4-4 Burst (Fast Transient)
Earth
Ground Ports
± 4 kV 4
Signal Ports ± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
4
DC Power Ports ± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
3
IEC 61000-4-5 Surge
AC Power Ports ± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
4
Signal Ports 10 V 3
DC Power Ports 10 V 3
AC Power Ports 10 V 3
IEC 61000-4-6 Induced (Conducted) RFI
Earth
Ground Ports
10 V 3
IEC 61000-4-8 Magnetic Field Enclosure Ports 40 A/m continuous, 1000 A/m for 1 s Note
a