EasyManuals Logo

Siemens RUGGEDCOM RMC30 User Manual

Siemens RUGGEDCOM RMC30
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
RUGGEDCOM RMC30
Installation Guide
Chapter 6
Certification
Other Approvals 25
CAN ICES-3 (A)/NMB-3 (A)
Section6.1.6
Other Approvals
This device meets the requirements of the following additional standards:
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3: General Requirements
Section6.2
EMC and Environmental Type Tests
The RUGGEDCOM RMC30 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test Description Test Levels Severity Levels
Enclosure Contact ± 8 kV 4IEC 61000-4-2 ESD
Enclosure Air ± 15 kV 4
IEC 61000-4-3 Radiated RFI Enclosure Ports 20 V/m Note
a
Signal Ports ± 4 kV @ 2.5 kHz Note
a
DC Power Ports ± 4 kV 4
AC Power Ports ± 4 kV 4
IEC 61000-4-4 Burst (Fast Transient)
Earth
Ground Ports
± 4 kV 4
Signal Ports ± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
4
DC Power Ports ± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
3
IEC 61000-4-5 Surge
AC Power Ports ± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
4
Signal Ports 10 V 3
DC Power Ports 10 V 3
AC Power Ports 10 V 3
IEC 61000-4-6 Induced (Conducted) RFI
Earth
Ground Ports
10 V 3
IEC 61000-4-8 Magnetic Field Enclosure Ports 40 A/m continuous, 1000 A/m for 1 s Note
a

Other manuals for Siemens RUGGEDCOM RMC30

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RUGGEDCOM RMC30 and is the answer not in the manual?

Siemens RUGGEDCOM RMC30 Specifications

General IconGeneral
BrandSiemens
ModelRUGGEDCOM RMC30
CategoryServer
LanguageEnglish

Related product manuals