EasyManuals Logo

Siemens RUGGEDCOM RS910 Installation Guide

Siemens RUGGEDCOM RS910
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
RUGGEDCOM RS910
Installation Guide
Chapter 2
Installing the Device
Connecting High AC/DC Power 9
Section2.3.2, “Connecting Low DC Power”
Section2.3.1
Connecting High AC/DC Power
To connect a high AC/DC power supply to the device, do the following:
CAUTION!
Electrical hazard – risk of damage to equipment. Do not connect AC power cables to terminals for DC
power. Damage to the power supply may occur.
CAUTION!
Electrical hazard – risk of damage to equipment. Before testing the dielectric strength (HIPOT) in the
field, remove the braided ground cable connected to the surge ground terminal and chassis ground.
This cable connects transient suppression circuitry to chassis ground and must be removed in order to
avoid damage to transient suppression circuitry during testing.
NOTE
Torque all terminal connections to 0.6 N·m (5 lbf-in).
1. Connect the positive wire from the power source to the positive/live (+/L) terminal on the terminal block.
4
1 2 3
Figure4:Terminal Block Wiring
1.Positive/Live (+/L) Terminal 2.Negative/Neutral (-/N) Terminal 3.Surge Ground Terminal 4.Braided Ground Cable

Other manuals for Siemens RUGGEDCOM RS910

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens RUGGEDCOM RS910 and is the answer not in the manual?

Siemens RUGGEDCOM RS910 Specifications

General IconGeneral
BrandSiemens
ModelRUGGEDCOM RS910
CategorySwitch
LanguageEnglish

Related product manuals