8. Configuration
0000
C111
7865p03/0200
Analog input 1
Pt100, 3-wire, IEC 751 0
Pt100, 2-wire, IEC 751 1
Ni100, 3-wire, DIN 43760 2
Ni100, 2-wire, DIN 43760 3
Landis & Staefa Pt1000, 3-wire, IEC 751 4
Landis & Staefa Pt1000, 2-wire, IEC 751 5
Ni1000, 3-wire, DIN 43760 6
Ni1000, 2-wire, DIN 43760 7
LG-Ni1000, 3-wire 8
LG-Ni1000, 2-wire 9
NiCr-Ni / K A
Cu-CuNi / T b
NiCroSil-NiSil / N C
Fe-CuNi / J d
Standard signal DC 0…20 mA E
Standard signal DC 4…20 mA F
Standard signal DC 0…10 V G
Standard signal DC 0…1 V H
Pt-RhPt / S ¹) i
Pt-RhPt / R ¹) j
Pt-RhPt / B ¹) L
Analog input 2
No function 0
External setpoint, 1 kW resistance potentiometer 1
External setpoint, DC 0…20 mA 2
External setpoint, DC 4…20 mA 3
External setpoint, DC 0…10 V 4
External setpoint, DC 0…1 V 5
Analog setpoint shift, 1 kW resistance potentiometer 6
Analog setpoint shift, DC 0…20 mA 7
Analog setpoint shift, DC 4…20 mA 8
Analog setpoint shift, DC 0…10 V 9
Analog setpoint shift, DC 0…1 V A
Position feedback resistance potentiometer 1 kW ¹) b
Position feedback 0...20 mA ¹) C
Position feedback 4...20 mA ¹) d
Position feedback 0...10 V ¹) E
Position feedback 0...1 V ¹) F
¹) Only with RWF40.0X2B97
8.1 C111 inputs