Safety regulations 
Introduction 
When used in plants or systems, SIMATIC TOP connect system cabling is subject to special 
rules and regulations in line with the area of application. 
This section provides an overview of the most important rules for connecting SIMATIC TOP 
connect. 
Rules and regulations governing the integration of the S7-1500 into a plant or system can 
also be found under "Rules and regulations" in the S7-1500 system manual 
(http://support.automation.siemens.com/WW/view/en/59191792
). 
Please observe the safety and accident prevention regulations that apply to specific 
applications, for example, the machinery directives. 
Please note the following points about line voltage: 
●  For stationary plants and systems without an all-pole line disconnector, there must be a 
disconnector unit (all-pole) fitted in the building installation. 
●  Any fluctuation/deviation in the line voltage from the rated value must be within the 
permitted tolerance for all S7-1500 electric circuits. 
Please note the following points for 24 V DC supply: 
●  Power supplies for 24 V DC must have secure electrical isolation in accordance with IEC 
60364-4-41. 
●  Surge arrestors must be fitted to protect against lighting and overvoltage. 
You will find components for lightning and overvoltage protection in the "Designing 
interference-free controllers" function manual 
(http://support.automation.siemens.com/WW/view/en/59193566
).