Wiring SIMATIC TOP connect to the I/O modules 
  5.5 Shield connection of the signal cables 
SIMATIC TOP connect for S7-1500 and ET200MP 
Manual,   
45 
 
Shield connection of the signal cables 
Shield connection options 
There are two options for grounding the signal cable shield: 
●  At the I/O module with the shield connection element of the front connector/front 
connector module; see S7-1500 function manual, Connections, Front connectors 
(http://support.automation.siemens.com/WW/view/en/59191792
) for the I/O modules. 
●  At the terminal module directly with a shield plate; see the description below. 
Attaching the shield plate to the terminal module 
The shield plate is used to connect the shield. 
1.  Position the shield plate on the back of the terminal module with the gaps in the shield 
plate fitted over the corresponding parts on the terminal module. 
 
Figure 5-1  Fit the shield plate over the back of the terminal module (example)