Technical specifications
6.4 Mechanical and climatic ambient conditions
SIMATIC TOP connect for S7-1500 and ET200MP
Manual,
53
Testing mechanical ambient conditions
Testing for...
Test standard
Remarks
Vibration Vibration test complying with
IEC 60068-2-6 (sine)
Vibration type: Frequency cycles with a rate
of change of 1 octave/minute.
5 Hz f 8.4 Hz, constant amplitude 7 mm
8.4 Hz f 150 Hz, constant acceleration
2 g
Vibration duration: 10 frequency cycles per
axis in each of the 3 axes which are
perpendicular to each other
Shock Shock, tested to IEC 60068-2-27 Type of shock: Half-sine
Shock intensity: 15 g peak value,
11 ms duration
Direction of shock: 3 shocks each in
+/direction in each of the three
perpendicular axes
Continuous shock Shock, tested to IEC 60068-2-27 Type of shock: Half-sine shock intensity:
250 m/s2 peak value, 6 ms duration
Direction of shock: 1000 shocks each in
+/direction in each of the three
perpendicular axes
Reduction of vibrations
If your SIMATIC TOP connect system cabling is exposed to severe shocks or vibration, take
appropriate measures to reduce the acceleration or amplitude. We recommend fitting the
SIMATIC TOP connect cabling system to shock-absorbent material (for example, metal
shock absorbers).
Ambient climatic conditions
SIMATIC TOP connect system cabling components may only be used in the ambient climatic
conditions specified in the technical specifications.
Please see the following sections.