Technical Specifications and Reference Information
A.4 Certificates, Directives and Declarations for the TD Device
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03
137
General TD400C
6AV6640-0AA00-0AX1
Noise immunity to high
frequency emission
10 V with 80% amplitude modulation at 1 kHz, 10 kHz to 80 MHz
10 V/m with 80% amplitude modulation at 1 kHz, 80 MHz to 1 GHz
3 V/m with 80% amplitude modulation at 1.4 GHz to 2 GHz
1 V/m with 80% amplitude modulation at 2.0 GHz to 2.7 GHz
Climatic Conditions
Temperature
Operation
Storage/Transport
0 to +50 °C
-20 to +60°C
Relative humidity
Operation
Storage/Transport
85% (30℃), no condensation
95% (25℃ to 55℃), no condensation
Mechanical Environmental Conditions
Vibration
Operation
Transport (packaged)
Tested according to IEC 60068-2-6
5 Hz to 9 Hz, amplitude, 3,5 mm
9 Hz to 150 Hz, acceleration 9.8 m/s2
5 Hz to 9 Hz, amplitude 3.5 mm,
9 Hz to 500 Hz, acceleration 9.8 m/s2
Shock
Operation
Transport (packaged)
Tested according to IEC 60068-2-27/29
Semisinusoidal: 150 m/s2 (15g), 11 ms
Semisinusoidal: 250 m/s2 (25g), 6 ms
Special Features
Quality assurance In accordance with ISO 9001
Servicing Maintenance-free (no battery)
Panel mounting Accessories for panel mounting are enclosed
A.4 Certificates, Directives and Declarations for the TD Device
Certificates, Directives and Declarations for the TD Device
IEC 61131-2
The TD 100C and TD400C devices satisfy the requirements and criteria of the IEC directive
2004/108/EC standard (programmable controllers, part 2 on equipment requirements and
tests).
Notes on the CE Symbol
The following applies to the SIMATIC product described in this operating
instruction