Technical Specifications and Reference Information
A.5 Approvals for USA, Canada and Australia
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03
139
A.5 Approvals for USA, Canada and Australia
Approvals for USA, Canada and Australia
The characters stamped on a device are indicative of the requirements which that device
meets:
Underwriters Laboratories: cULus Approval, Hazardous Location
cULus Listed 21BP I.T.E. for Hazardous Location
Underwriters Laboratories Inc., according to:
● TD 200 and TD 200C:
UL 60950 (Information Technology)
CSA C22.2 No. 60950 (Information Technology)
cULus Listed 7RA9 IND. Cont. EQ. for Hazardous Location
Underwriters Laboratories Inc., according to:
● TD 100C and TD400C
UL 508 (Industrial Control Equipment)
CSA C22.2 No. 142 (Industrial Control Equipment)
UL 1604 (Hazardous Location)
CSA-213 (Hazardous Location)
APPROVED for use in:
● CI. I, Div.2, GP. A, B, C, D, T5
● CI. I, Zone 2, GP.IIC, T5
Please see the note below:
Note
This plant has to be mounted according to the NEC (National Electric Code) stipulations.
When used in environments according to class I, division 2 (see above), the SIMATIC TD
device must be mounted in a housing that corresponds to at least IP54 according to EN
60529.
FM approval to Factory Mutual Approval Standard Class Number 3611, Class I,
Division 2, Group A, B, C, D, and Class I, Zone 2, Group IIC.
Temperature Class T5 is adhered to when the ambient temperature during
operation does not exceed 50 degrees C
Note for Australia: The TD 100C, TD 200, and TD 200C devices fulfil the
requirements for Norm AS/NZS CISPR 22. The TD400C device fulfils the
requirements for Norm AS/NZS CISPR 11.