Connecting Multiple Devices on a Network
B.7 CPU Grounding and Circuit Reference Point Guidelines for Using Isolated Circuits
Text Display (TD) User Manual
System Manual, 08/2008, A5E00765548-03
161
DC digital inputs and outputs are isolated from logic circuit to 500 VAC.
DC digital I/O groups are isolated from each other by 500 VAC.
Relay outputs are isolated from logic circuit to 1,500 VAC.
Relay output groups are isolated from each other by 1,500 VAC.
AC power supply line and neutral are isolated from ground, the logic circuit, and all I/O to
1,500 VAC.