Installing your Text Display (TD) Device
2.2 Components Shipped with the TD Devices
Text Display (TD) User Manual
32 System Manual, 08/2008, A5E00765548-03
The TD 100C and TD 200C ship with a blank faceplate that you can customize. The
TD 100C, TD 200C and TD400C ship with a pre-printed faceplate for the standard TD
keypad. The faceplate is constructed from durable, polyester material which has been
designed specifically for use for HMI faceplates.
Tip
To print your custom-designed image onto the blank faceplate material, you must use a laser
printer that supports the printing of transparencies on both A4 and envelope formats and
also supports color printing.
General TD Installation Information
Tip
To ensure compliance with IP 65 or UL 50 Type 4X:
The minimum panel thickness must be at least 1.5 mm.
For the TD 200, TD 200C, and TD400C, the mounting screws must be tightened to a
torque of 0.7 N-m.
For the TD 100C, the mounting screws must be tightened to a torque of 0.2 Nm (about
0.5 mm the height of the seal).
The gasket must be replaced whenever the TD device is removed and reinstalled.
To procure new gaskets, contact your Siemens distributor or sales representative.
The TD 100C, TD 200, TD 200C, and TD400C devices are suitable for use in Class I,
Division 2, Groups A, B, C, D; Class I, Zone 2, Group IIC; or non-hazardous locations.
WARNING
WARNING - EXPLOSION HAZARD!
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS LOCATION IS KNOWN TO BE
NON-HAZARDOUS
WARNING
WARNING - EXPLOSION HAZARD!
Substitution of components may impair suitability for Class I, Division 2 or Zone 2.