System Overview
26 SICAM RTUs, SICAM MIC System Description
MC6-054-2.00, Edition 07.2014
2.4 Communication
2.4.1 Process Communication and Engineering
Via the communication interface(s), the master control element can communicate with any
superior or subordinate automation unit using an external data transmission facility, or directly
via LAN/WAN.
Master Control Interface Remarks
CP-6020/CPC60 RS-232
*)
Process communication and engineering use the serial
interface exclusively, and therefore are not available simul-
taneously
CP-6040/CPC60
· RS-232
· Ethernet LAN
Process communication is not available simultaneously
using both interfaces
*)
with supply for external modem
The following transmission facilities can be supplied directly from the power supply module us-
ing a special cable.
Type Designation Power (typ.) Supply
1)
CE-0700 V.23 leased line modem 400 mW 5 V
CE-0701
2)
VFT channel modem 2 W 5 V
MODEM ANALOG Analog modem for dial-up traffic 35 mW 10 V
MODEM GSM Dual band GSM modem 300 mW 10 V
1)
switchable by means of TM bus message to the power supply module
2)
withdrawn