System Components and Technical Data
56 SICAM RTUs, SICAM MIC System Description
MC6-054-2.00, Edition 07.2014
5.4.1  Acquisition and Preprocessing
5.4.1.1  DI-6100 ,DI-6101, DI-6104
·  Single-point information
─  Acquisition with a resolution of 10 ms
t
─  Update every 10 ms
a
 (in the cycle of the open-/closed-loop control function, if larger)
─ Revision
ta
─  Power monitoring
ta
─ Inversion
ta
─  Firmware filter
t
─  Bounce suppression
t
─  Determination of the cause of transmission
t
─  Spontaneous transmission of changes
t
─  Periodical transmission
a
·  Double-point information
─  Acquisition with a resolution of 10 ms
t
─  Update every 10 ms
a
 (in the cycle of the open-/closed-loop control function, if larger)
─ Revision
ta
─  Power monitoring
ta
─ Inversion
ta
─  Firmware filter
t
─  Bounce suppression
t
─  Monitoring intermediate and faulty positions
t
─  Determination of the cause of transmission
t
─  Reporting switching operations in progress
t
─  Breaker tripping detection
t
─  Breaker tripping suppression during auto-reclose
t
─  Spontaneous transmission of changes
t
─  Periodical transmission
a
·  Integrated totals via count pulses
t1
─  Acquisition by firmware with a maximum count frequency of 20 Hz
−  Pulse length/pause  >20 ms/>20 ms
− Revision
−  Power monitoring
− Inversion
−  Pulse counting
─  Counter value formation
−  Count pulse evaluation
−  Set counter
─  Formation of integrated totals
−  Counter request
−  Interval control
−  Frozen absolute value
−  Frozen relative value
─  Not power-fail safe
─  Integrated total transmission according to iec 60870-5-101
─  Spontaneous transmission