System Components and Technical Data
62 SICAM RTUs, SICAM MIC System Description
MC6-054-2.00, Edition 07.2014
5.4.2.3  DO-6220, DO-6221, DO-6230
·  Pulse commands
 t1
─  Checked output of pulse commands
−  1-pole, 1½-pole, 2-pole
−  Cannot be mixed on one module
─  Single, double and regulating step commands
─  Application functions and procedures according to IEC 60870-5-101/104
−  Formal check
−  Direct command
−  Select and execute command ("select/execute")
─  Control location check
─  Retry suppression
─  1-out-of-n check
─  Command locking
─ Synchronization
─ Revision
─  DO-6220 - command output according to IC1
−  Idle check
−  Selective activation check
─  DO-6221 - command output according to RC1
−  Idle check
−  Selective activation check
−  Resistance check
−  Current flow information
−  Earth fault check
−  Interference voltage check
─  Command output time
− Settable
−  Dependent on the process
─  Return information monitoring
─  Command prolongation
─  Periodical control circuit check
─  Switching sequences
─  Monitoring of command output sequence to prevent incorrect outputs
─  Command initionation for auto-reclose
─  Activation of command contactors with or without series-break contacts (with DO-6221)
5.4.2.3.1  Further Functions
·  Return information to pulse command assignment (applies only for DO-6230)
─  Settable assignment
─  Predefined assignment