System Components and Technical Data
SICAM RTUs, SICAM MIC System Description 59
MC6-054-2.00, Edition 07.2014
5.4.1.4 AI-6310
· Temperatures
t1
─  Acquisition of resistance thermometers via analog inputs of a SM-0571
─  Connection of the resistance thermometers: 2-, 3-, or 4-wire technique
─  Update every 400 ms
─  Settable measuring range
− Temperaturwerte
-  Input range
Pt100:    -50…+350°C / -58…+662°F / (»80,31…229,67 Ω)
Pt100:  -100…+700°C / -148…+1292°F / (»60,25…345,13 Ω)
Ni100:    -60…+250°C / -76…+482°F / (»69,5…289,2 Ω)
- Resolution
Pt100:    -50…+350°C  0.15°C / 0.28°F / (56 mΩ)
Pt100:  -100…+700°C  0.15°C / 0.28°F / (56 mΩ)
Ni100:    -60…+250°C  0.15°C / 0.28°F / (56 mΩ)
-  Update grid
16⅔ Hz  <6,8 s
50 Hz     < 5,6 s
60 Hz     < 5,2 s
−  Resistance values
-  Input range 40…400 Ω
-  Resolution 56 mΩ
-  Update grid
HW rev. ="--" HW rev. ≥"-A"
16⅔ Hz   < 6,8 s  16⅔ Hz   < 1,68 s
50 Hz      < 5,6 s  50 Hz      < 1,44 s
60 Hz      < 5,2 s  60 Hz      < 1,36 s
─  Revision
─  Noise rejection
*)
─  Automatic calibration
─  Calibration for 2-wire technique
─ Smoothing
─ Adaptation
−  Temperature value (°C, °F), conversion using implemented curves
−  Resistance (Ω)
─  Change monitoring
─  Spontaneous transmission of changes
______
*)
  not supported by USIO60, USIO61
5.4.1.5 TE-6430
·  Integrated totals via counting pulses
─  2 counting pulse inputs or
─  1 counting pulse input and 1 transfer input
─  Inputs are galvanically insulated from logic circles and ground
─  Inputs are not galvanically insulated from each other
─  Input voltage range from 24 up to 60 V
─  Inputs are secured by means of EMC filter and protector equipment
─  Autonomous operable functions of the module are operated buffered, thus counting func-
tion and counts remain correct with a voltage failure up to 72 hours
─  Spontaneous transmission
 f