System Overview
SICAM RTUs, SICAM MIC System Description 27
MC6-054-2.00, Edition 07.2014
2.4.2  Transmission Modes
Depending on master control module there are different communication methods available:
·  Multi-point traffic
·  Dial-up traffic
·  Communication via LAN/WAN
·  Communication via Intranet/GPRS
Features and transmission facilities with pre-defined settings:
Type Features Transmission Facilities
Multi-Point Traffic
·  Unbalanced interchange circuit
(V.24/V.28) up to 19.2 kbps
(depends on the used data transmis-
sion device)
·  Time synchronization via serial inter-
face
·  Efficient message transmission ac-
cording to IEC 60870-5-101 ("se-
quence of information objects")
·  Proprietary function "relay operation
with routing"
·  Modems with 4-wire and 2-wire
technology (CE-0700 and CE-
0701)
 1)
·  DLC Modem (CM-0740, CM-0741)
· SAT DMS
·  Direct connection RS-232
· Digital radio
· Analog radio
· CM-0827 optical
Dial-Up Traffic
·  Unbalanced interchange circuit
(V.24/V.28) up to 19.2 kbps
(depends on the used data transmis-
sion device)
·  Time synchronization via serial inter-
face
·  Efficient message transmission ac-
cording to IEC 60870-5-101 ("se-
quence of information objects")
·  SMS (messages) when using a GSM
data transmission device
· Coherent Technologies
Eurocom 24 (analog)
1)
·  Cinterion MC52iT (GSM
900/1800 MHz)
2)
·  Siemens M20 Databox, TC35
(GSM 900/1800 MHz)
 2)
·  Westermo TD-36 (analog)
·  Westermo IDW-90 (ISDN)
·  Sepura Terminal (TETRA)
·  Insys GSM 4.1 (GSM)
LAN/WAN
·  10 Mbit/s Ethernet according to IEEE
802.3, 10Base-TX
·  Time synchronisation with an NTP
server via LAN/WAN
·  Message transmission according to
IEC 60870-5-104
· Siemens MD741-1
·  Dr. Neuhaus Tainy EMOD-V2-IO
(GPRS)
3)
·  Dr. Neuhaus Tainy EMOD-L1-IO
(GPRS)
3) 4)
GPRS
1)
  supply 5 V via modem cable SICAM MIC for CE-070x
2)
  supply 10 V via modem cable SICAM MIC for MC52iT-Modem
3)
  transmission of SMS (notifications) possible
4)
  without IP sec. VPN tunnel