Ambient Conditions
SICAM RTUs, SICAM MIC System Description 43
MC6-054-2.00, Edition 07.2014
4.4 Electromagnetic Compatibility
4.4.1  System Properties
Parameter Value Test standard Cl. Product stand. Cl.
Discharge of static elec-
tricity (ESD)
8 kV-L
6 kV-K
IEC 61000-4-2 IEC 60870-2-1 3
IEC 60255-22-2 3
Electromagnetic fields 10 V/m IEC 61000-4-3 IEC 60870-2-1 3
IEC 60255-22-3 3
50 Hz magnetic fields 30 A/m IEC 61000-4-8 IEC 60870-2-1 3
Pulse-shaped magnetic
fields
300 A/m IEC 61000-4-9 IEC 60870-2-1
Radio interference field
strength (10 m)
40/47 dBµV CISPR22 IEC 60870-2-1 A
CISPR22 A