Siemens SIMATIC 6DL1193-6AG00-0AA0 - Table B-2 Derating When Devices Are Used at an Elevation above Sea Level

Siemens SIMATIC 6DL1193-6AG00-0AA0
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ambient condi‐
tions
Permissible range Comments
Concentration of
pollutants
SO
2
: <0.5 ppm
RH: <60%, no condensation
H
2
S: <0.1 ppm
RH: <60%, no condensation
Test: 10 ppm; 4 days
Test: 1 ppm; 4 days
ISA-S71.04 severity level G1; G2; G3 -
Derating
The cooling e󹪜ect of air decreases at higher altitudes as a result of its lower density.
The table shows the derating factor for the maximum permissible ambient temperature
depending on the use of the devices at an elevation above sea level.
Table B-2 Derating when devices are used at an elevation above sea level
Elevation above sea level
1)
Derating factor for ambient temperature
2)
(-1 000 m) up to 2 000 m 1.0
3 000 m 0.9
4 000 m 0.8
1)
Note that I/O modules with relay contacts are only suitable for an elevation up to 3 000 m.
2)
Relating to the maximum permissible ambient temperature in °C for 2 000 m
Technical speci󹪝cations
B.1 Ambient conditions
BusAdapter for Distributed I/O
40 Equipment Manual, 10/2021, A5E39261458-AC