Wiring
3.3 Configuring PROFIBUS DP address and terminating resistor
IM 157-1 DP (6ES7157-1AA00-0AB0)
18 Equipment Manual, 08/2021, A5E32100641-AE
Setting the PROFIBUS DP address
Configurable PROFIBUS DP addresses are 1 to 99.
Proceed as follows to configure the PROFIBUS DP address:
1. Remove the two M12 sealing caps from the rotary coding switches
(use 14 mm socket wrench, if needed).
2. Configure the desired PROFIBUS DP address with a screwdriver on the rotary coding
switches.
Top rotary coding switch: Tens digit
Bottom rotary coding switch: Ones digit
3. Screw the two M12 sealing caps back onto the thread to protect the rotary coding switches
(torque: 0.5 to 0.8 Nm).
4. Switch the supply voltage off and on again (POWER OFF/POWER ON).
The figure below shows the rotary coding switches for configuring the PROFIBUS DP address.
Rotary coding switch for PROFIBUS DP (tens digit)
Rotary coding switch for PROFIBUS DP address (ones digit)
Figure 3-2 Setting the PROFIBUS address