Counting
4.1 Configuration method 2xCount
Digital input/Digital output module DIQ 16x24VDC/0.5A 8xM12 (6ES7143-5AH00-0BA0)
36 Manual, 03/2019, A5E38688112-AC
4.1.2 Parameters/address space
4.1.2.1 Parameters
In the configuration method 2xCount of the digital input / digital output module
DIQ 16x24VDC/0.5A 8xM12 the Channels 0 to 7 are used by the counting function. The
Channels 8 to 15 can be parameterized freely.
The following table shows the general parameter of the module.
Table 4- 7 General parameters
Parameters
Value range
Default
Scope
Diagnostics: Missing load volt-
age 2L+
Disable
Enable
Disable Module
Diagnostics: Short-circuit to
ground
Disable
Enable
Disable Module
(Short-circuit of
encoder supply or
of the output to
ground)
Behavior at CPU/master STOP
(8...15)
Shut down
Keep last value
Output substitute value
Shut down Module
(digital outputs)