PROFIenergy
6.4 Behavior of the digital inputs of the counters
Digital input/Digital output module DIQ 16x24VDC/0.5A 8xM12 (6ES7143-5AH00-0BA0)
Manual, 03/2019, A5E38688112-AC
83
6.4 Behavior of the digital inputs of the counters
Display
The channel status LEDs are directly influenced by the signal level at the socket.
If the encoder supply is switched off, this causes the channel status LEDs to also switch off.
Response to error detection
All channels that are in pause mode on "PE_MODE_PROCEED" report their diagnostic
status as in productive mode.
The following applies for all channels which switch to a different pause mode:
● Encoder supply switch-off upon the start of "pause" does not result in the "Short-circuit"
alarms.
● During the "pause", error detection of "Short circuit" is not possible:
– Alarms for errors already pending before the "pause" are retained.
– After the "pause" is over, the error status is updated and incoming/outgoing errors are
reported correspondingly.
Note
Channels of a counter
All the channels that belong to a counter must have the same PROFIenergy behavior.
If substitute value behavior is parameterized, this also has to be the same for all channels of
a counter.
ior is not the same for all the channels of a counter, the module
rejects the PROFIenergy parameterization.
Further information on the assignment of the counting channels for the configuration method
2xCount is available in the section
Pin assignment (Page 33), for the configuration method
Pin assignment (Page 53).