Parameters/address space
4.2 Explanation of the parameters
Communication module CM 8x IO-Link + DI 4x24VDC M12-L (6ES7148-6JG00-0BB0
24 Equipment Manual, 09/2020, A5E49284833-AA
Operating mode
This parameter determines the mode in which the selected port should be operated.
You can select from the following options:
IO-Link autostart
IO-Link manual
IO-Link autostart
The connected IO-Link device starts automatically (Plug&Play functionality). The IO-Link
device is immediately ready for operation.
IO-Link manual
The connected IO-Link device is not started automatically.
You must store the Vendor ID and Device ID of the connected IO-Link device in STEP 7.
Inspection Level/Data Storage
You can select the inspection level for data storage:
Identical type (V1.0) without Backup&Restore
Type-compatible (V1.1) without Backup&Restore
Type-compatible (V1.1) with Backup&Restore
Type-compatible (V1.1) with Restore
Port cycle time
Set the IO-Link cycle time at the corresponding port.
See also
You can find out more about the vendor ID and the device ID of an IO-Link device on the
Internet (https://support.industry.siemens.com/cs/ww/en/view/109748852).