ET 200pro distributed I/O EtherNet/IP interface module
Manual, 03/2016, A5E32861915-AB
17
The ET 200pro EtherNet/IP module
3
3.1
ET 200pro EtherNet/IP module hardware
Hardware configuration
You can operate your ET 200pro EtherNet/IP module in automatic configuration mode, or
you can use the EIP ET200 Configuration Tool software to operate in user configured mode.
The software and associated User Reference Guide can be found on the companion disk
that shipped with your module, or downloaded from the Siemens Industry Online Support
(https://support.automation.siemens.com/cs/?lc=en-US) website.
LED status indicators
The ET 200pro EtherNet/IP module has three bi-color LEDs that provide diagnostic
information about the current state of the device and provide an indication of any faults. The
LEDs conform to the behaviors defined in the ODVA EtherNet/IP Adaptation of CIP Adapter
Specification for the Module Status and Network Status LEDs, and in this manual for I/O
Status LEDs.
LED status indicator: Module Status LED
The bi-color Module Status LED indicates the current state of the ET 200pro EtherNet/IP
module, as described in the following table:
State
Description
Off No power applied to device.
Flashing green Device has not been configured.
Invalid parameter data.
Green Device has initialized successfully and no errors
were detected.
Flashing red Recoverable fault.
Device needs
commissioning due to configuration
error:
• Invalid parameter data
• Invalid slot configuration data.
Red
Unrecoverable fault detected: hardware failure.