The ET 200pro EtherNet/IP module
3.8 Device profile: vendor-specific objects
ET 200pro distributed I/O EtherNet/IP interface module
Manual, 03/2016, A5E32861915-AB
41
3.8
Device profile: vendor-specific objects
3.8.1
Adapter Object
The Adapter Object provides the external configuration and monitoring interface to the
ET 200pro EtherNet/IP.
Class code
0x64
Class attributes
No attributes are supported
for the Adapter Object at the class level.
Number of instances
1
Instance 1 attributes of the Adapter Object
Attribute
ID
Access rule
Name
Data type
Data value
1 Get AdapterStatus USINT Adapter Status (see AdapterStatus details
table).
2
Get
InputSize
USINT
Currently configured input assembly size.
3 Get OutputSize USINT Currently configured output assembly size.
4 Get/Set
2
AutoConfig BOOL Automatic Configuration mode
1: Automatic configuration: the rack self-
configures based on the modules installed
(factory default).
0: Manual configuration: the rack configuration
is stored in nonvolatile memory.
5 Get ConfigChanged BOOL True if manual configuration changes have
been made but have not taken effect.
6 Get Diagnostic String Array of USINT
[65]
An array of USINT containing slot diagnostics.
The first byte of the array indicates the number
of valid diagnostic bytes within the array (the
remaining bytes within the array can be ig-
nored).
7
Get
ConfiguredSlots
USINT
Indicates the number of configured slot objects.
8 Get/Set
2
HeadParameters Array of USINT
[19]
Configuration information for the adapter mod-
ule.
9 Get/Set
2
IO_StatusEnable BOOL Enables the generation of an I/O status byte at
the beginning of the input data I/O packet.
Factory default = enabled.
10
Get/Set
2
HeadParamByte1
USINT
Parameter bytes for electronic module and
adapter module behavior.
11
Get/Set
2
HeadParamByte2
USINT
12 Get/Set
2
HeadParamByte3 USINT
13
Get/Set
2
HeadParamByte4
USINT
14 Get/Set
2
HeadParamByte5 USINT
15
Get/Set
2
HeadParamByte6
USINT
16
Get/Set
2
HeadParamByte7
USINT

Table of Contents