The ET 200pro EtherNet/IP module
3.7 Device profile: supported CIP objects
ET 200pro distributed I/O EtherNet/IP interface module
Manual, 03/2016, A5E32861915-AB
39
Instance 1 attributes for EtherNet Link Object
Attribute
ID
Access
rule
Name
Description
Data type
Semantics of values
1 Get Interface
Speed
Interface speed cur-
rently in use
UDINT Speed in Mbps (10, 100,
etc.).
2 Get Interface
Flags
Interface status flags DWORD Bit map of interface flags.
See Table "Interface Flags
attribute" below.
3 Get Physical
Address
MAC layer address ARRAY
of 6
USINTs
MAC layer address
in the format
"XX-XX-XX-XX-XX-XX."
6 Set Interface
Control
Configuration for physi-
cal interface
STRUCT
of:
See section "Interface
Control" below.
Control Bits
Interface Control Bits
WORD
----
Forced
Interface
Speed
Speed at which the
interface shall be
forced to operate
UINT Speed in Mbps (10, 100,
etc.).
Interface Flags attribute
Bit(s):
Called:
Definition
0 Link Status Indicates whether the IEEE 802.3 communications interface is
connected to an active network:
0 = inactive link.
1 = active link.
The determination of link status is implementation specific.
1 Half/Full Duplex Indicates the duplex mode currently in use:
0 = interface is running half duplex.
1 = interface is running full duplex.
Note that if the Link Status flag is 0, the value of the half/full duplex
flag is indeterminate.
2 - 4 Negotiation Status Indicates the status of link autonegotiation:
0 = autonegotiation in progress.
1 = autonegotiation and speed detection failed. Using default val-
ues for speed and duplex.
2 = autonegotiation failed but detected speed. Duplex was faulted.
3 = successfully negotiated speed and duplex.
4 = autonegotiation not attempted. Forced speed and duplex.
5 Manual Setting Re-
quires Reset
0 = interface can activate changes to link parameters (autonegoti-
ate, duplex mode, interface speed) automatically.
1 = device requires a Reset service be issued to its Identity Object
in order for the changes to take effect.
6 Local Hardware Fault 0 = interface detects no local hardware fault.
1 = local hardware fault detected.
7 - 31
Reserved
Set to 0.