Wiring
CPU 1510SP-1 PN (6ES7510-1DJ01-0AB0)
Equipment Manual, 05/2021, A5E03506268-AD
23
Assignment of the MAC addresses
The MAC address is a globally unique device identifier that is assigned to each PROFINET
device in the factory. Its 6 bytes are divided into 3 bytes for the manufacturer ID and 3 bytes
for the device ID (serial number). The front of the CPU 1510SP-1 PN is lasered with the MAC
address of the PROFINET interface.
The PROFINET interface (X1) of the CPU 1510SP-1 PN has three ports. Port 3 is located on the
CPU. Ports 1 and 2 are located on the optional BusAdapter. In addition to the PROFINET
interface, each PROFINET port also has a separate MAC address. There is therefore a total of
four MAC addresses for the CPU 1510SP-1 PN.
The MAC addresses of the PROFINET ports are needed for the LLDP protocol, for example for
the neighborhood discovery function.
The table below shows how the MAC addresses are assigned.
Table 3- 4 Assignment of the MAC addresses
Assignment
MAC address 1
PROFINET interface X1
Visible in STEP 7 for accessible devices
Lasered on the front of the CPU
(start of the number range)
MAC address 2
Port X1 P1 R (required for LLDP, for example)
MAC address 3
Port X1 P2 R (required for LLDP, for example)
MAC address 4
Port X1 P3 (required for LLDP, for example)

Other manuals for Siemens simatic et200sp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic et200sp and is the answer not in the manual?

Siemens simatic et200sp Specifications

General IconGeneral
CategoryI/O Systems
Power Supply24 V DC
Protection RatingIP20
Number of ModulesUp to 64 modules
MountingDIN Rail
Communication ProtocolsPROFINET, PROFIBUS
Storage Temperature-40 °C to +70 °C
Digital InputsYes (depending on module)
Digital OutputsYes (depending on module)
Analog InputsYes (depending on module)
Analog OutputsYes (depending on module)
ModularityModular
Relative Humidity5 to 95% (non-condensing)
WeightVaries by configuration
System TypeDistributed I/O

Related product manuals