Commissioning a project   
6.7 OS update - Basic Panel PN 
  Basic Panels 
106  Operating Instructions, 04/2012, A5E02421799-03 
6.7.2  Resetting factory settings 
In ProSave, WinCC flexible or WinCC, you can update the operating system with or without 
resetting to factory settings.  
●  Updating the operating system without reset to factory settings 
First, switch into "Transfer" mode on the HMI device or use the automatic transfer 
function if the project is active. Then start the operating system update in ProSave, 
WinCC flexible or WinCC.  
●  Updating the operating system with reset to factory setting 
NOTICE 
 
 
Data channel  
When resetting to factory settings, all data channel parameters used are reset. The 
transfer can only be started following reconfiguration of the data channel. 
 
 
Note 
You have to perform an operating system update with reset to factory setting if the HMI 
device does not yet have an operating system or if the HMI device's operating system is 
corrupt. 
First, start the operating system update in ProSave, WinCC flexible or WinCC, and switch 
the power on the HMI device off and on again when prompted. 
See also 
Data transmission options (Page 91) 
6.7.3  Updating the operating system using WinCC flexible 
If possible, you should use the interface with the highest bandwidth for this connection, such 
as Ethernet. Updating the operating system via a serial connection can take up to an hour. 
 
CAUTION 
 
Updating the operating system deletes all data on the HMI device 
When you update the operating system you delete data on the target system. For this 
reason, it is advisable to backup the following data: 
•  User administration 
•  Recipes 
Resetting to factory settings also deletes the License Keys. You should also back up the 
License Keys before resetting to factory settings.