Certification
6.2EMC and Environmental Type Tests
Test Description Test Levels Severity Levels
IEC 61000-4-17 Ripple on DC
Power Supply
DC Power Ports 10% 3
IEC 61000-4-18 Damped
Oscillatory Wave
Slow Damped 2.5 kV Common
Mode on Power
and Signal
1.0 kV Differential
Mode on Power
3
IEC 61000-4-29 Voltage Dips
and Interrupts
DC Power Ports 30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal Ports 2 kV (Fail-Safe
Relay Output)
DC Power Ports 2 kV
Dielectric Strength
AC Power Ports 2 kV
Signal Ports 5 kV (Fail-Safe
Relay Output)
DC Power Ports
IEC 60255-27
HV Impulse
AC Power Ports
5 kV
a
Siemens-specified severity levels
EMC Immunity Type Tests per IEEE 1613
Note
RUGGEDCOM products meet Class 1 requirements for copper Ethernet
configurations and Class 2 for fiber Ethernet configurations. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Description Test Levels
Enclosure Contact ±2 kV
±4 kV
±8 kV
ESD
Enclosure Air ±4 kV
±8 kV
±15 kV
Radiated RFI Enclosure Ports 35 V/m
Signal Ports 4 kV @ 2.5 kHz
DC Power Ports 4 kV
AC Power Ports 4 kV
Fast Transient
Earth Ground Ports 4 kV
Signal Ports 2.5 kV Common Mode @ 1 MHz
DC Power Ports 2.5 kV Common
1 kV differential mode @ 1 MHz
Oscillatory
AC Power Ports 2.5 kV Common
44
RUGGEDCOM RSG2100
Installation Manual, 11/2022, C79000-G8976-1040-20