Special functions of the CPU 410 
  9.13 Updating firmware in redundant mode 
CPU 410 Process Automation/CPU 410 SMART 
System Manual, 05/2017, A5E31622160-AC 
149 
Proceed as follows to activate the loaded firmware at a later time: 
1.  Open the station containing the CPU you want to update in HW Config. 
2.  Select the CPU. 
3.  Select the "PLC -> Update firmware" menu command. 
4.  Make sure that the same firmware version as the loaded firmware has been loaded to 
both CPUs. 
The version of the loaded firmware is displayed in the "Update firmware" dialog. 
5.  Select "Activate loaded firmware" and click "Execute". 
The CPU in rack 1 is switched to STOP 
The new firmware is activated in the CPU in rack 1 
6.  Click "Continue". 
The system switches to the CPU with the new firmware. 
The new firmware is activated in the CPU in rack 0. 
The CPU in rack 0 is started. 
The CPU in rack 0 is linked up and updated. 
Both CPUs have updated firmware (operating system) and are in the redundant operating 
state. 
Firmware update in one stage 
Proceed as follows to update the firmware of the CPUs of a fault-tolerant system in RUN: 
1.  For CPU access protection with password: Select a CPU of the fault-tolerant system in 
SIMATIC Manager and select menu command 
PLC > Access Authorization > Setup. Enter the CPU access password. 
2.  Select the CPU. 
3.  Open the station containing the CPU you want to update in HW Config. 
4.  Select the "PLC -> Update firmware" menu command. 
5.  In the "Update Firmware" dialog, select the path to the firmware update files (*.UPD) 
using the "Browse" button. 
After you have selected a file, the information in the bottom boxes of the "Update 
Firmware" dialog box indicates the modules for which the file is suitable and as of which 
firmware version. 
6.  Select "Load and activate firmware".