System expansion card
15
15.1
Variants of the system expansion card
Use of the system expansion card
The system expansion card (SEC) is inserted in a slot at the back of the CPU.
The SEC is used to scale the CPU 410 to correspond the maximum loadable process
objects. More detailed information about the scaling concept can be found in the section
Scaling and licensing (scaling concept) (Page 32).
Operation of the CPU is not possible without an SEC. If no valid SEC is detected, the
corresponding CPU does not start up.
If an error occurs in redundant mode during access to the SEC of a CPU, this triggers a loss
of synchronization and a startup block prevents another automatic link-up. You cannot
operate two CPUs 410 redundantly with two different SECs.
System Expansion Card for CPU 410-5H
SECs with the following number of PO are available for the CPU 410-5H:
0
You must store the required number of POs on this SEC before the first use.
100
500
1000
1600
2k+ (unlimited)
System Expansion Card for CPU 410E
An SEC with the following number of PO is available for the CPU 410E:
200

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 and is the answer not in the manual?

Siemens SIMATIC PCS 7 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7
CategoryControl Systems
LanguageEnglish

Related product manuals