Connection examples for redundant I/Os 
  C.19 SM 322; DO 32 x DC 24 V/0,5 A, 6ES7 322–1BL00–0AA0 
CPU 410 Process Automation/CPU 410 SMART 
System Manual, 05/2017, A5E31622160-AC 
409 
 
SM 322; DO 32 x DC 24 V/0,5 A, 6ES7 322–1BL00–0AA0 
The diagram below shows the connection of an actuator to two redundant SM 322; DO 32 x 
DC 24 V. The actuator is connected to channel 1.  
Suitable diodes are, for example, those of the series 1N4003 ... 1N4007, or any other diode 
with U
_r 
>=200 V and I_
F 
>= 1 A 
 
Figure C-17  Example of an interconnection with SM 322; DO 32 x DC 24 V/0.5 A