I/O configuration variants   
6.7 Connection of two-channel I/O to the PROFIBUS DP interface 
  CPU 410 Process Automation/CPU 410 SMART 
94  System Manual, 05/2017, A5E31622160-AC 
Redundant analog input modules for direct current measurement  
The following applies for wiring analog input modules: 
●  Suitable encoder types: active 4-wire and passive 2-wire transmitters with output ranges 
+/-20 mA, 0 to 20 mA, and 4 to 20 mA. 2-wire transmitters are powered by an external 
auxiliary voltage. 
●  The "wire break" diagnostics function supports only the 4...20 mA input range. All other 
unipolar or bipolar ranges are excluded in this case. 
●  Suitable diodes include the types of the BZX85 or 1N47..A series (1.3 W Zener diodes) 
with the voltages specified for the modules. When selecting other elements, make sure 
that the reverse current is as low as possible. 
●  A fundamental measuring error of max. 1 µA results from this type of circuit and the 
specified diodes due to the reverse current. In the 20 mA range and at a resolution of 
16 bits, this value leads to an error of < 2 bits. Individual analog inputs in the circuit above 
lead to an additional error, which may be listed in the constraints. The errors specified in 
the manual must be added to these errors for all modules. 
●  The 4-wire transmitters used must be capable of driving the load resulting from the circuit 
above. You will find details in the technical specifications of the individual modules. 
●  When connecting 2-wire transmitters, please note that the Zener diode circuit weighs 
heavily in the power budget of the transmitter. The required input voltages are therefore 
included in the technical specifications of the individual modules. Together with the 
inherent supply specified on the transmitter data sheet, the minimum supply voltage is 
calculated to L+ > U
e-2w 
+ U
IS-TR
 
Redundant analog input modules with redundant encoders  
With double-redundant encoders, it is better to use fail-safe analog input modules in a 1-out-
of-2 configuration: 
 
Figure 6-18  Fault-tolerant analog input modules in 1-out-of-2 configuration with two encoders 
The use of redundant encoders also increases their availability. 
A discrepancy analysis also detects external errors, except for the failure of a non-redundant 
load voltage supply. 
You will find interconnection examples in Appendix Connection examples for redundant I/Os 
(Page 391). 
The general comments made at the beginning of this documentation apply.