Plant changes in RUN - CiR 
  11.8 Procedure for PROFIBUS DP 
CPU 410 Process Automation/CPU 410 SMART 
System Manual, 05/2017, A5E31622160-AC 
173 
The following basic operating steps are available in STOP state:  
●  Defining CiR elements 
●  Deleting CiR elements 
●  Editing CiR elements 
●  Downloading the configuration 
You can define CiR objects for previously configured DP and PA master systems and CiR 
modules for modular DP slaves of type ET 200M / ET 200iSP. For the exact procedure, see 
Defining CiR elements. 
The "Activate CiR capability" function is additionally available for DP master systems. If you 
select this function, a CiR object is created on the selected DP master system and on each 
CiR-capable lower-level PA master system. A CiR module is inserted on each CiR-capable 
modular slave of type ET 200M / ET 200iSP on the selected DP master system. 
 
Note 
The "Activate CiR capability" function is only possible on DP master systems on which a CiR 
object is not yet defined.
 
In STOP operating state, you can delete CiR objects on DP and PA master systems or CiR 
modules on modular DP slaves of type ET 200M / ET 200iSP that you have defined 
previously. 
If you want to delete all CiR elements in a DP master system, you can easily do this using 
the "Deactivate CiR capability" function. 
 
Note 
The "Deactivate CiR capability" function is only possible for DP master systems on which a 
CiR object is defined.
 
Downloading the configuration 
After defining new CiR elements or redefining existing CiR elements, you download the 
configuration with the CPU in STOP operating state. 
A large number of modules can be used in the S7-410 automation system. To ensure that 
none of the modules you are using will prevent a future CiR action, you must adhere to the 
following procedure: Once you have downloaded the configuration in STOP operating state 
of the CPU, immediately download it again to the CPU, but this time with the CPU in RUN 
operating state. When this is done, STEP 7 and the CPU will check the CiR capability. With 
older modules or modules from third-party manufacturers, this is not yet possible offline.