Supplementary information 
  18.7 Communication services 
CPU 410 Process Automation/CPU 410 SMART 
System Manual, 05/2017, A5E31622160-AC 
309 
Allocation of S7 connection 
resources 
PROFINET IO  Data exchange between I/O controllers 
No  No  Yes 
SNMP 
(Simple Network Manage-
Standard protocol for network diagnos-
tics and parameter assignment 
No  No  Yes 
Open communication over 
TCP/IP 
Data exchange over Industrial Ethernet 
with TCP/IP protocol (with loadable 
Yes  No  Yes 
Open communication over 
ISO on TCP 
Data exchange over Industrial Ethernet 
with ISO on TCP protocol (with 
Yes  No  Yes 
Open communication over 
Data exchange over Industrial Ethernet 
with UDP protocol (with loadable FBs) 
Yes  No  Yes 
Data record routing  For example, parameter assignment 
and diagnostics of field devices on 
Yes  Yes  Yes 
 
 
Note 
Communication via an PNIO interface 
If you want to use an PNIO interface of the module for communication in system operation, 
you must also network this in Step 7 / HW Config / NetPro.
 
Availability of connection resources  
Table 18- 5  Availability of connection resources 
Total number of  
connection resources 
Can be used for 
S7-H connections 
Reserved from the total number for  
Free S7 connections can be used for any of the above communication services. 
 
Note 
Communication service via the PROFIBUS DP interface 
A fixed default timeout of 40
 s is specified for communication services using S7 connection 
resources. If you operate those communication services via a PROFIBUS DP interface at a 
low baud rate, operation in configurations with a Ttr (Target Rotation Time) < 20
 s is