Supplementary information 
  18.13 Link-up and update sequence 
CPU 410 Process Automation/CPU 410 SMART 
System Manual, 05/2017, A5E31622160-AC 
349 
9.  Transfer of outputs and of all data block contents modified again. Transfer of timers, 
counters, bit memories, and inputs. Transfer of the diagnostic buffer. 
During this data synchronization, the system interrupts the clock pulse for cyclic 
interrupts, time-delay interrupts and S7 timers. This results in the loss of any synchronism 
between cyclic and time-of-day interrupts. 
10.Cancel all restrictions. Delayed interrupts and communication functions are executed. All 
OBs are executed again. 
A constant bus cycle time compared with previous calls can no longer be guaranteed for 
delayed cyclic interrupt OBs. 
 
Note 
Process interrupts and diagnostic interrupts are stored by the I/O devices. Such interrupt 
requests issued by distributed I/O modules are executed
 when the block is re-enabled. 
Any such requests by central I/O modules can only be executed provided the same 
interrupt request did not occur repeatedly while the status was disabled.
 
If the PG/ES requested a master/standby changeover, the previous standby CPU assumes 
master mode and the previous master CPU goes into STOP when the update is completed. 
Both CPUs will otherwise go into RUN (redundant system mode) and execute the user 
program in synchronism. 
When there is a master/standby changeover, in the first cycle after the update OB 1 is 
assigned a separate identifier (see 
System Software for S7-300/400, System and Standard 
Functions
 Reference Manual). For information on other aspects resulting from modifying the 
configuration, refer to section Switch to CPU with modified configuration (Page 351). 
Delayed message functions  
The listed SFCs, SFBs and operating system services trigger the output of messages to all 
logged-on partners. These functions are delayed after the start of the update: 
●  SFC 17 "ALARM_SQ", SFC 18 "ALARM_S", SFC 107 "ALARM_DQ", SFC 108 
"ALARM_D" 
●  SFC 52 "WR_USMSG" 
●  SFB 31 "NOTIFY_8P", SFB 33 "ALARM", SFB 34 "ALARM_8", SFB 35 "ALARM_8P", 
SFB 36 "NOTIFY", SFB 37 "AR_SEND" 
●  Process control alarms 
●  System diagnostics messages 
From this time on, any requests to enable and disable messages by SFC 9 "EN_MSG" and 
SFC 10 "DIS_MSG" are rejected with a negative return value.