Supplementary information 
  18.16 CPU 410 cycle and reaction times 
CPU 410 Process Automation/CPU 410 SMART 
System Manual, 05/2017, A5E31622160-AC 
371 
Calculation of the actual cycle time 
●  Allowance for communication load (default value: 20%):  
 18.419 ms * 100 / (100–20) 
. 
●  There is no interrupt processing. 
So the actual, cycle time is approx. 
. 
Calculating the longest response time 
●  Longest response time  
 23.024 ms * 2 
. 
●  The delay of the inputs and outputs is negligible. 
●  All the components are plugged into the central controller; DP cycle times do not 
therefore have to be taken into account. 
●  There is no interrupt processing. 
So the longest, rounded up response time is 
. 
You have installed an S7-400 with the following modules: 
●  a CPU 410–5H in redundant mode 
●  4 digital input modules SM 421; DI 32×DC 24 V (each with 4 bytes in the PI) 
●  3 digital output modules SM 422; DO 16xDC 24 V /2 (each with 2 bytes in the PI) 
●  2 analog input modules SM 431; AI 8x13 bit (not in the PI) 
●  2 analog output modules SM 432; AO 8x13 bit (not in the PI) 
The CPU parameters were assigned as follows: 
●  Cycle load due to communication: 40% 
According to the instruction list, the user program runtime is 10.0 ms.