I/O configuration variants 
  6.5 Using single-channel switched I/O 
CPU 410 Process Automation/CPU 410 SMART 
System Manual, 05/2017, A5E31622160-AC 
69 
The FF Link bus link is a gateway between a PROFIBUS DP master system and a 
FOUNDATION Fieldbus H1 segment and thus enables the integration of FF devices in 
SIMATIC PCS 7. The two bus systems are uncoupled from each other by the IM 153-2 FF 
both physically (galvanically) and with respect to protocol and time. 
The FF Link bus link consists of one or two IM 153-2 FF interface modules and an FDC 157 
field device coupler or a redundant FDC 157 coupler pair, which are connected to one 
another via passive bus connectors or, in the case of the redundant installation, via bus 
modules. 
The Compact FF Link bus link consists of one or two IM 655-5 FF interface modules. 
 
IM 153-2 
6ES7153-2DA80-0XB0 
Compact FF Link  6ES7655-5BA00-0AB0 
A single-channel switched I/O configuration must always be symmetrical.  
●  This means the fault-tolerant CPU and other DP masters must be installed in the same 
slots in both subsystems (for example slot 4 in both subsystems) or 
●  The DP slaves must be connected to the same DP interface in both subsystems (for 
example to the PROFIBUS DP interfaces of both fault-tolerant CPUs).