I/O configuration variants 
  6.5 Using single-channel switched I/O 
CPU 410 Process Automation/CPU 410 SMART 
System Manual, 05/2017, A5E31622160-AC 
71 
PROFINET IO interfaces are located on two different IMs, this is known as an R1 
configuration The R stands for redundant IMs and thus for two PROFINET IO interfaces. See 
Chapter Communication services (Page 308). 
You can use the following interface module for the I/O configuration at the PROFINET IO 
interface: 
Table 6- 5  Interface module for use of single-channel switched I/O configuration at the PROFINET 
IO interface 
IM 153-4 PN V4.0 and higher 
IM 155-6 PN HA  6DL1155-6AU00-0PM0 
Single-channel switched I/O and user program 
In redundant operation, in principle any subsystem can access single-channel switched I/O. 
The data is automatically transferred via the synchronization link and compared. An identical 
value is available to the two subsystems at all times owing to the synchronized access. 
If you have connected the I/O over two IMs, the CPU accesses the I/O over one IM. The 
active IM is indicated by illumination of the ACT LED. 
The path via the currently active DP interface or PROFINET IO interface is called the 
, while the path via the other interface is called the 
. The DP or PNIO 
cycle is always active on both channels. However, only the input and output values of the 
active channel are processed in the user program or output to the I/O. The same applies to 
asynchronous activities, such as interrupt processing and the exchange of data records. 
Failure of the single-channel switched I/O  
The fault-tolerant system with single-channel switched I/O responds to errors as follows: 
●  The faulty I/O is no longer available if an input/output module or a connected device fails. 
●  In certain failure situations (for example failure of a subsystem, a DP master system or an 
IM153-2 DP slave interface), the single-channel switched I/O continues to be available for 
the process. 
This is achieved by a changeover between active and passive channel. This changeover 
takes place separately for each DP or PNIO station. A distinction is made between the 
following two types of failure: 
–  Failures affecting only one station (such as failure of the DP slave interface of the 
channel currently active) 
–  Failures affecting all stations of a DP master system or PNIO system 
These include removal of the connector at the DP master interface or PNIO interface, 
shutdown of the DP master system (for example a RUN-STOP transition on a CP 443-
5), and short-circuits at the cable harness of a DP master system or PNIO system. 
The following applies to each station affected by a failure: If both DP slave interfaces or PN 
IO connections are functional and the active channel fails, the channel previously passive 
automatically becomes the active channel. A redundancy loss is reported to the user 
program when OB 70 starts (event W#16#73A3).