I/O configuration variants   
6.7 Connection of two-channel I/O to the PROFIBUS DP interface 
  CPU 410 Process Automation/CPU 410 SMART 
96  System Manual, 05/2017, A5E31622160-AC 
A configured substitute value of 0 mA will produce at least these output values. In a 
redundant configuration of analog outputs, the substitute value of the current outputs is 
automatically set permanently to "zero current and zero voltage". You can also specify a 
configurable compensation current of 0-400 µA for an output range of 4-20 mA. 
This means you have the option of matching the minimum/compensation current to the 
connected I/O. 
To minimize the error of the total current at the summing point in case of one-sided 
passivation, the assigned compensation current is subtracted in this case from the current of 
the depassivated (i.e., active) channel with a pre-set value of 4 mA (range +-20 µA). 
 
Note 
If both channels of a channel pair were passivated (e.g., by OB 85), the respective half of the 
current value is still output to both storage locations in the process image of outputs. If one 
channel is depassivated, then the full value is output on the available channel. If this is not 
required, a substitute value must be writte
n to the lower channels of both modules prior to 
executing FB 451 "RED_OUT".
 
Passivated modules are depassivated by the following events: 
●  When the fault-tolerant system starts up 
●  When the fault-tolerant system switched to "redundant" mode 
●  After system modifications during operation 
●  If you call FC 451 "RED_DEPA" and at least one redundant channel or module is 
passivated. 
The depassivation is executed in FB 450 "RED IN" after one of these events has occurred. 
Completion of the depassivation of all modules is logged in the diagnostics buffer. 
 
Note 
When a redundant module is assigned a process image partition and the corresponding OB 
is not available on the CPU, the complete passivation process may take approximately 1 
minute.
 
 
SIMATIC Process Control System PCS 7 Released Modules 
(https://support.industry.siemens.com/cs/ww/de/view/109736547/en) 
S7-400H Systems Redundant I/O 
(http://support.automation.siemens.com/WW/view/en/9275191)