Procedure
Step Action
1
● In the Component view in SIMATIC Manager , open the "S7 Program(1)/Charts" folder 
in the "fast_Lib"  master data library.
● Select the "MotorLean" CFC chart. In the shortcut menu, select the menu command 
"Rename". Enter the object name "MOTOR1" .
● Select the "ValveLean" CFC chart. In the shortcut menu, select the menu command 
"Rename". Enter the object name "VALVE1" .
● Select the "PIDConL_ConPerMon" CFC chart. In the shortcut menu, select the menu 
command "Rename". Enter the object name "PIDCTRL1" .
After being renamed, the process tag types become process tags.
2
● Double-click on the "MOTOR1" CFC chart.
The CFC Editor opens.
● Connect the "Start" parameter of the "Motor" block to the "SimPV_In" parameter of the 
"FbkRun" block. Proceed as follows:
– Left-click on the "Start" parameter and keep the mouse button pressed.
– Move the cursor to the "SimPV_In" parameter until an arrow symbol appears.
– Release the mouse button.
● Double-click on the "Sim_On" parameter on the "FbkRun" block.
The "Select Structure Element" dialog box opens.
● Double-click the "Value ..." line.
The "Properties - Input/Output" dialog box opens.
● Change the entry in the "Value" input box to 1.
● Click "OK".
The "Properties - Input/Output" dialog box closes.
● Click "Close".
The "Select Structure Element" dialog box closes.
● In the CFC Editor, select the menu command Chart > Close.
Configuring the process tags and the sequential control
4.2 How to create a project-specific CFC chart
Getting Started (V8.1 with APL)
32 Getting Started, 07/2014, A5E32713210-AA