EasyManua.ls Logo

Siemens SIMATIC PCS 7 - Device List Information

Siemens SIMATIC PCS 7
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.3 How to Copy the CFC Charts into the Project
Introduction
Now copy the adapted and renamed CFC charts from the "fast_Lib" master data library in the
"fast_Prj" project to the plant's "Function (1)" folder. When you have completed copying you
can continue with configuration in SIMATIC Manager in the Process Object view.
Requirement
The project-specific CFC charts "MOTOR1", "VALVE1" and "PIDCTRL1" are located in the
"Charts" folder of the master data library in the Process Object View.
SIMATIC Manager is open in the Component View.
Procedure
Step Action
1 Select the menu command "View > Plant View" in SIMATIC Manager.
2 In the Plant View, open the tree in the left-hand window.
3 Select the "Process tag types" folder in the "fast_Lib" folder.
4 In SIMATIC Manager, select the menu command "Window > Arrange > Tile vertically".
5 In the Component View, select the folder "fast_Lib" > S7 Program(1) > Charts
6 Keeping <CTRL> pressed, select the 3 charts "MOTOR1", "VALVE1" and "PIDCTRL1".
7 Open the shortcut menu and select the menu command "Cut".
8 Select the "Process tag types" folder in the Plant View.
9 Open the shortcut menu and select the menu command "Paste".
The 3 charts are now located in the "Process tag types" folder in the Plant View.
10 In the SIMATIC Manager, select the menu command "View > Process Object View".
11 In the Process Object View, open the tree in the left-hand window.
12 Click the "Process tag types" folder in the "fast_Lib" folder.
13 In the right window, open the "General " tab.
The following CFCs are displayed in the table:
"MOTOR1"
"VALVE1"
"PIDCTRL1"
14 Select all 3 charts.
To do this, click on the row number in the first column.
Drag-and-drop the selected CFC charts to the "fast_Prj\Plant(1)\Unit(1)\Function(1)" folder.
Note:
You can select multiple charts by simultaneously pressing the <Ctrl> key.
15 Click on the folder "fast_Prj\Plant(1)\Unit(1)\Function(1)".
The copied CFCs are shown in the table in the right-hand window.
Configuring the process tags and the sequential control