Step Action
12
● Change to keyset 2 by clicking "Keyset change" on the bottom left of the user
interface.
13
● Click "SFC Visualization" in key set 2.
The "Open SFC" dialog box opens.
14
● In the right window, select the "CONTROL1" entry in the "SFC Name" column and click
"OK".
The SFC overview is displayed in the work area.
● Click the "Start" button and confirm the dialog box that appears by clicking "OK".
If the process value of the controller is not higher than 50, the sequential control system
stops at the first transition and is not executed further.
– Click on the faceplate of the "PIDCTRL1/PID" controller (see picture below
"Executing the sequential control system").
– Click on the input box next to "Setpoint" in the faceplate of the controller. The faceplate
is expanded. Enter "80" as the setpoint. Click "OK".
15
● Observe the execution of the sequential control system.
– When the configuration is correct, the sequential control system is executed
completely.
– MOTOR1 is started in the flow chart in step 3 and stopped again in step 4.
16
● Click "Keyset change" to change to keyset 1.
17
● Click the "Message System" button.
The new received messages are displayed in the work area.
18
● Click "Operation List".
The operating messages are displayed in the work area. The list displays all
actions you have performed in the faceplates.
Operating and monitoring the process
10.1 How to operate and monitor the process
Getting Started (V8.1 with APL)
Getting Started, 07/2014, A5E32713210-AA 59