Programming
5.1 Programming with STEP 7 (TIA Portal)
Technology module TM FAST (6ES7554-1AA00-0AB0)
40 Equipment Manual, 04/2023, A5E52301130-AA
Status parameter
Error codes or status information are output as word at the Status output.
Code
Meaning Remedy
(W#16#...)
0000
No error.
7000
No job in progress.
7001
Initialization in progress.
7002
The data is being read.
8001
An error has occurred in the WRREC or RDREC instruc-
tion.
Read the description of the WRREC/RDREC in the
information system of STEP 7 (TIA Portal) (error
code in static tag AdditionalErrorID).
8002
An error has occurred when reading the data block.
Check the UserlogicDB input parameter.
Check the db file.
8003
An error has occurred when reading the upd file from
the SIMATIC Memory Card.
Check the FilenameSMC input parameter.
Check the upd file.
Ensure that the upd file name does not con-
tain a special character or a space.
8004
An error has occurred when using the read-out data.
Check the upd or db file.
8005
The user logic in the TM FAST application if defective.
Check the upd or db file.
8006
An invalid state has occurred.
If the error permanently occurs, contact support.