Configuring/address space
4.3 Operation of the commissioning editor
Technology module TM FAST (6ES7554-1AA00-0AB0)
26 Equipment Manual, 04/2023, A5E52301130-AA
4.3 Operation of the commissioning editor
The commissioning editor helps you to conveniently commission the technology module. You
control the TM FAST application and read its status information via the commissioning editor.
Explanation of the functions
Parameter
Description
TM FAST module status
FPGA status
Indicates the current state of the FPGA:
TM FAST application is loaded and active: The TM FAST ap-
plication was successfully loaded from the flash memory in-
to FPGA and has been activated.
TM FAST application is loaded but not active: The TM FAST
application was successfully loaded from the flash memory
into FPGA, has not yet been activated though.
No TM FAST application available: There is no TM FAST ap-
plication in the FPGA, for example in these cases:
Before loading an TM FAST application for the first time.
After the command "Remove TM FAST application from
FPGA"
Last error code
Displays the error code (Page 63) of the last error that occurred
(in conjunction with the FPGA).
Debug interface status
Display the current state of the debug interface:
Debug interface enabled: The access to the FPGA via
TM FAST Debug Connector has been enabled.
Debug interface disabled: The access to the FPGA via
TM FAST Debug Connector has been blocked.
Internal temperature
Displays the internal temperature of the module. This value
provides the option to check whether the application, in con-
junction with the ambient temperature, will overload the mod-
ule in the long term. A critical temperature range starts from
90 °C.
Command status
Indicates whether the current command is still being processed.
If the command is still being processed, click "Read status" again
after a few seconds. Only after the current command has been
processed is it possible to send a new command.