Data record TMFASTControlREC
C.2 Validation error with data record 100
Technology module TM FAST (6ES7554-1AA00-0AB0)
Equipment Manual, 04/2023, A5E52301130-AA
67
C.2 Validation error with data record 100
The technology module checks the transferred data record. If the technology module detects
invalid or inconsistent values, it outputs an error code (STATUS output parameter of the
WRREC/RDREC instruction). You can find information on using WRREC/RDREC in the section
Parameter validation error with data record 128 (Page 61).
Error codes
The following table shows the module-specific error codes and their meaning for data record
100.
Error code in the
STATUS parameter (hexadec-
imal)
Meaning
Remedy
Byte
0
Byte
1
Byte
2
Byte
3
DF
80
B0
00
Data record number unknown
Enter valid number for data record
DF
80
B1
01
Length of data record incorrect
Enter valid value for data record length.
DF
80
B2
00
Slot invalid or not accessible
Check whether module is inserted or removed.
Check assigned values for parameters of the
WRREC/RDREC instruction.
DF
80
A7
00
New command not yet possible because previ-
ous command is still being processed
Wait until new command is possible (read Byte 1 Bit
4).
DF
80
A9
00
"Command" parameter invalid
Enter valid parameter value.
DF
80
D4
00
Wrong version
Check byte 0.
Enter valid values.