EasyManua.ls Logo

Siemens Simatic S7-1500 / ET 200MP - Page 67

Siemens Simatic S7-1500 / ET 200MP
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data record TMFASTControlREC
C.1 Use and structure of TMFASTControlREC (data record 100)
Technology module TM FAST (6ES7554-1AA00-0AB0)
66 Equipment Manual, 04/2023, A5E52301130-AA
Last error code
The following table shows the FPGA-specific error codes.
Error
code
Meaning Remedy
00H
No error
01H
Communication with TM FAST application
failed
Update TM FAST application
02H
03H
04H
05H
06H
07H
TM FAST application cannot be activated
Load TM FAST application into the FPGA
08
H
TM FAST application cannot be removed
from FPGA. Possible reason: Hardware de-
fect
Check hardware
09
H
No TM FAST application available in the flash
memory
Update TM FAST application in the flash
memory
0AH
Communication with TM FAST application
failed
Update TM FAST application
0BH
0C
H
Function ID ≠ 0
Set value of function ID to 0
Set value of FUNCTION_ID to 0 system
logic parameter

Other manuals for Siemens Simatic S7-1500 / ET 200MP

Related product manuals