Interrupts/diagnostic alarms
6.1 Status and error displays
Technology module TM FAST (6ES7554-1AA00-0AB0)
46 Equipment Manual, 04/2023, A5E52301130-AA
Meaning of the LED displays
The following tables explain the meaning of the status and error displays. Remedial measures
for diagnostic alarms can be found in the section Diagnostic alarms (Page 48).
Table 6- 1 Status and error displays RUN/ERROR/MAINT
Meaning Remedy
Off
Off
Off
No voltage or too low voltage on back-
plane bus
• Switch on the CPU and/or the system
power supply modules.
• Check whether the voltage connect-
ors are inserted.
• Check whether too many modules
are inserted.
Technology module not configured
Technology module configured but no
module diagnostics
On
Flashes
Off
Technology module configured and
module diagnostics (at least one error
Evaluate the diagnostic alarms and elim-
inate the error.
Hardware or firmware defective
Replace the technology module.
On
Off
On
FPGA debug interface enabled
Disable the FPGA debug interface (e.g.
via the commissioning editor) and re-
move the TM FAST Debug Connector as
soon as the commissioning of the mod-
Table 6- 2 PWR/ERROR status displays
Meaning Remedy
Off
Off
Supply voltage too low or missing
and "Missing supply voltage L+" not
activated
• Check the supply voltage.
• Make sure that the front connect-
or is correctly inserted.
• Activate "Missing supply voltage
L+" in the device configuration.
Off
Flashes
Supply voltage too low or missing
• Check the supply voltage.
• Make sure that the front connect-
or is correctly inserted.
Supply voltage is present and OK
Module diagnostics (at least one
error is present)
Evaluate the diagnostic alarms and
eliminate the error.