Interrupts/diagnostic alarms
6.2 Diagnostic alarms
Technology module TM FAST (6ES7554-1AA00-0AB0)
Equipment Manual, 04/2023, A5E52301130-AA
49
Diagnostic alarms
The diagnostics are displayed as plain text in STEP 7 (TIA Portal) in the online and diagnostics
view. You can evaluate the error codes with the user program. System-wise, the module is
modeled with only one channel containing all terminals. Therefore, "Channel 0" is always
indicated in the diagnostic message independent of the terminal from which the respective
diagnostic starts.
Note
"Channel 0" means the entire module in the diagnostics. In the description of the front
connector and the logic, however, "Channel" refers to an RS485/TTL channel.
The following diagnostics can be signaled:
Table 6- 5 Diagnostic alarms, their meaning and remedies
Diagnostic
alarm
Error
code
Meaning Remedy
Parameter assign-
ment error
10
H
Received parameter data record invalid
Check parameter data record
Supply voltage
missing
11
H
Undervoltage
Check supply voltage L+
Wiring of supply voltage L+ faulty
Check wiring of supply voltage L+
Supply voltage L+ of the technology module
missing
Feed supply voltage L+ to the technology
module via terminal 41
Front connector not inserted correctly
Insert front connector correctly
Internal error
100H
Technology module defective
Replace technology module
Watchdog tripped.
Module is defec-
tive.
103
H
Firmware error
Run firmware update
Technology module defective
Replace technology module
Error at digital
outputs
1
10F
H
Error at digital outputs (LED DQm display
lights up red)
Possible causes:
Short-circuit
Overload
Correct wiring at the digital outputs
Check consumers connected to the
digital outputs
RS422/TTL error
502
H
Error at the connection of an RS485/TTL
channel
Possible causes:
Wire break
No encoder connected
Cable too long
Short-circuit
Overload
External voltage
Overtemperature
Parameter assignment error
Check process wiring
Check encoder/sensor
Check parameter assignment