Parameter data record
B.2 Parameter validation error with data record 128
Technology module TM FAST (6ES7554-1AA00-0AB0)
62 Equipment Manual, 04/2023, A5E52301130-AA
Error codes
The following table shows the module-specific error codes and their meaning for data record
128.
Error code in the
STATUS parameter (hexadec-
imal)
Meaning
Remedy
Byte
0
Byte
1
Byte
2
Byte
3
DF
80
B0
00
Data record number unknown
Enter valid number for data record
DF
80
B1
01
Length of data record incorrect
Enter value 32D.
DF
80
B2
00
Slot invalid or not accessible
Check whether module is inserted or removed.
Check assigned values for parameters of the
WRREC instruction.
DF
80
E0
01
Wrong version
Check byte 0.
Enter valid values.
DF
80
E0
02
Length of the parameter data not correct
Enter value 28D.
DF
80
E1
F0
At least one reserved bit is not set to 0.
Set all reserved bits to 0.
DF
80
E1
01
"Input delay DIm" parameter invalid
Enter valid parameter value.
DF
80
E1
02
"Input delay CHm" parameter invalid
Enter valid parameter value.
DF
80
E1
03
"Bus terminating resistor CH2" enabled
"Bus terminating resistor CH3" enabled
"Bus terminating resistor CH5" enabled
"Bus terminating resistor CH6" enabled
"Bus terminating resistor CH7" enabled
Enter value 0 for bus terminating resistors CH2, CH3,
CH5, CH6 and CH7.