Parameter data record
B.2 Parameter validation error with data record 128
Technology module TM FAST (6ES7554-1AA00-0AB0)
62 Equipment Manual, 04/2023, A5E52301130-AA
Error codes
The following table shows the module-specific error codes and their meaning for data record
128.
STATUS parameter (hexadec-
Data record number unknown
Enter valid number for data record
Length of data record incorrect
Slot invalid or not accessible
• Check whether module is inserted or removed.
• Check assigned values for parameters of the
WRREC instruction.
• Check byte 0.
• Enter valid values.
Length of the parameter data not correct
At least one reserved bit is not set to 0.
Set all reserved bits to 0.
"Input delay DIm" parameter invalid
Enter valid parameter value.
"Input delay CHm" parameter invalid
Enter valid parameter value.
• "Bus terminating resistor CH2" enabled
• "Bus terminating resistor CH3" enabled
• "Bus terminating resistor CH5" enabled
• "Bus terminating resistor CH6" enabled
"Bus terminating resistor CH7" enabled
Enter value 0 for bus terminating resistors CH2, CH3,
CH5, CH6 and CH7.