● To ensure optimal stability, the clearance between the two DIN rail adapters must be no
more than 250mm or less.
Figure 6-6Distance between two DIN rail adapters
NOTE
Note that, depending on the mounting rail width, the mounting rail adapter can protrude up
to 4mm on each side due to the drill holes.
You can find an overview of the protrusion dimensions for the various DIN rails in the table
below.
Table 6-3Additional lateral space required
Mounting rail Article No. Additional space required with
adapter
• 160.0mm (with drill holes) 6ES7590‑1AB60‑0AA0 4mm
• 245.0mm (with drill holes) 6ES7590‑1AC40‑0AA0 4mm
• 482.6mm (with drill holes) 6ES7590‑1AE80‑0AA0 8mm
• 530.0mm 6ES7590‑1AF30‑0AA0 0mm
• 830.0mm (with drill holes) 6ES7590‑1AJ30‑0AA0 0mm
162
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Installation
6.3 Installing the standard rail adapter