EasyManuals Logo

Siemens SIMATIC S7-1500T Safety Programming Guideline

Siemens SIMATIC S7-1500T
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
2 Configuring Fail-Safe Controllers
Safety Programming Guideline
Entry ID: 109750255, V1.0, 10/2017
6
Siemens AG 2017 All rights reserved
2 Configuring Fail-Safe Controllers
2.1 Selecting the suitable F-CPU
Selecting the F-CPU depends on the following factors:
Runtime of the safety program
PROFIsafe communication time
Response time of the safety function
Number of required inputs and outputs
Number of connected I/O devices
Estimate of the response time
If you already have a rough idea of the automation system you want to use, you
can estimate the response time of your safety program using the SIMATIC STEP 7
Reaction Time Table or go through various scenarios to select the suitable F-CPU:
https://support.industry.siemens.com/cs/ww/en/view/93839056
Figure 2-1: Reaction time wizard of the SIMATIC STEP 7 Reaction Time Table
Influence of the safety program's cycle time on the standard user program
A long cycle time of the safety program slows down the response time of your
safety functions, but allows more time for processing the standard user program.
A short cycle time of the safety program increases the response time of your safety
functions, but allows less time for processing the standard user program.

Other manuals for Siemens SIMATIC S7-1500T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500T and is the answer not in the manual?

Siemens SIMATIC S7-1500T Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-1500T
CategoryController
LanguageEnglish

Related product manuals